Sign In | Join Free | My himfr.com
Home > Thermal Overload Relay >

UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay

    Buy cheap UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay from wholesalers
     
    Buy cheap UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay from wholesalers
    • Buy cheap UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay from wholesalers
    • Buy cheap UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay from wholesalers

    UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay

    Ask Lasest Price
    Brand Name : KRIPAL
    Model Number : UKH-40
    Certification : CE, UL
    Price : negotiable
    Payment Terms : T/T, L/C
    Supply Ability : 30000 pcs per month
    Delivery Time : 20 days and depends on ordering quantity
    • Product Details
    • Company Profile

    UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay


    UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay


    UKH series thermal overload relays apply to circuit of AC 50Hz or 60Hz, rated voltage to below 660V and rated current . 1A-800A for AC motor overload and open-phase protection during long time or intermittent long time service, which can also protect 3-phase serious imbalance and long starting time of motor or long timer operation, can also be used for corresponding AC contactor for electromagnetic starter.


    Applications:


    Thermal overload relays are economic electromechanical protection devices for the main circuit.

    They offer reliable protection for motors in the event of overload or phase failure.

    The thermal overload relay can make up a compact starting solution together with contactors.


    Specifications:


    Type

    Thermal component

    Rated current (A)

    Range of rated current (A)

    UKH-40

    UKK-40

    5

    4.0-6.0

    6.5

    5.0-8.0

    7.5

    6.0-9.0

    8.5

    7.0-10.0

    11

    9.0-13.0

    15

    12.0-18.0

    19

    16.0-22.0

    22

    18.0-26.0

    30

    24.0-36.0

    34

    28.0-40.0


    Motion Characteristic:


    Three-phase Balance Motion Time

    No

    Times of the setting current

    Motion time

    Start condition

    Ambient temperature

    1

    1.05

    >2h

    Cold state

    20±5oC

    2

    1.2

    <2h

    Heat state(Following the No.1 test)

    3

    1.5

    <4min

    4

    7.2

    10A

    2s< Tp≤10s

    ≤63A

    Cold state

    10

    4s< Tp≤10s

    >63A


    Phase-losing Motion Characteristic

    No

    Times of the setting current

    Motion time

    Start condition

    Ambient temperature

    Any two phases

    Another phase

    1

    1.0

    0.9

    >2h

    Cold state

    20±5oC

    2

    1.15

    0

    <2h

    Heat state(Following the No.1 test)


    Working Principle of Thermal Relay:


    A thermal relay works depending upon the coefficient of expansion of metals. The basic working principle of thermal relay is that, when a bimetallic strip is heated up by a heating coil carrying over current of the system, it bends and makes normally open contacts.


    Main benefits:


    1. Reliable protection for motors

    2. Easy to create starters

    3. Optimized match to UKC1 series contactors

    4. Single mounting kits and wire reset for remote control available for specific applications.


    Main features:


    1. Trip class 10

    2. Adjustable current setting ranges

    3. Overload protection with phase loss sensitivity

    4. Temperature compensation up to +60°C

    5. Automatic or manual reset, sealable