Sign In | Join Free | My himfr.com
Home > AC Contactor >

Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

    Buy cheap Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed from wholesalers
     
    Buy cheap Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed from wholesalers
    • Buy cheap Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed from wholesalers
    • Buy cheap Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed from wholesalers

    Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

    Ask Lasest Price
    Brand Name : KRIPAL
    Model Number : UKC1-22
    Certification : CE, UL
    Price : negotiable
    Payment Terms : T/T, L/C
    Supply Ability : 50000 pcs per month
    Delivery Time : 20 days and depends on ordering quantity
    • Product Details
    • Company Profile

    Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed


    Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed


    A Ccontactor is an electrically controlled switch used for switching a power circuit, similar to a relay except with higher current ratings, which is controlled by a circuit which has a much lower power level than the switched circuit.


    Description:


    UKC1 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC50Hz or 60Hz,

    rated current up to 630A, for making, breaking, frequently starting & controlling the AC motor. Combined with

    the auxiliary contact block, timer delay & machine interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter.


    With the thermal overload relay, it is combined into the electromagnetic starter. The product conforms to

    IEC60947-4-1 standard.


    Characteristics


    1. The cover for preventing electrical shock on the top of ac contactor and thermal overload relay


    2. The ac contactor and relay are classified into 3 frame sizes according to the external dimensions


    3. AC Contactor and relay can be connected directly without other fittings


    4. Installed by screws or on the 35mm DIN rail directly


    Specifications:

    ModelUKC1-9UKC1-12UKC1-18UKC1-22
    AC coilUKC1-9UKC1-12UKC1-18UKC1-22
    DC coilUKD1-9UKD1-12UKD1-18UKD1-22
    IEC-60947AC1 Load25A25A40A40A
    AC3 Load200~240V2.5KW 11A3.5KW13A4.5KW18A5.5KW 22A
    380~440V4KW 9A5.5KW12A7.5KW18A11KW 22A
    500~550V4KW 7A7.5KW12A7.5KW13A15KW 22A
    690V4KW 5A7.5KW 9A7.5KW 9A15KW 18A
    UL508Current (Ith)20A25A30A32A
    Single phase115V0.5HP0.5HP1HP2HP
    230V1Hp2Hp3Hp3Hp
    Three phase200V2HP3HP5HP7.5HP
    230V2HP3HP5HP7.5HP
    460V5HP7.5HP10HP10HP
    575V7.5HP10HP15HP15HP


    Coil voltage(AC) :

    50Hz: 24V, 42V, 48V, 100V, 110V, 220V, 240V, 380V, 400V, 415V, 440V, 500V, 550V
    60Hz: 24V, 48V, 110V, 120V, 208V, 220V, 240V, 277V, 380V, 440V, 480V, 600V



    Coil voltage(DC):

    12V, 20V, 24V, 48V, 60V, 80V, 100V, 110V, 125V, 200V, 220V, 250V


    Installation & Connection:


    Installation: Fixed by 35mm guide rail or screw (M4)
    Connection: Main contact: Screw(M4)crimping terminal; Wire diameter: 2-14mm2