    Ask Lasest Price
    Brand Name : KRIPAL
    Model Number : UKL7
    Certification : CE
    Price : negotiable
    Payment Terms : T/T, L/C
    Supply Ability : 200000 pcs per month
    Delivery Time : 20 days and depends on ordering quantity
    • Product Details
    • Company Profile

    1P+N 10kA Residual Circuit Breaker 2 Pole with Over Current RCBO


    1P+N 10kA Residual Circuit Breaker 2 Pole with Over Current RCBO


    Description:


    Residual circuit breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage. leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short-circuited as wellas infrequent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917


    Main features:


    1. Action function independent of the voltage of main circuit


    2. The neutral line breaking could make the device after and more reliable


    3. Dual-function wiring terminal with strong wiring capability


    4. The indicator for contact state help identification of contact condition


    5. Different hand handle color is to indicate the rated current


    6. Wide rated current scope to serve as general switch at home service


    Specitifcation:

    Technology Specification & Electrical Specification
    Electric standardIEC61009; GB 16917.0
    Trip timeNon-time delay; Minimal 10ms time delay
    Rated voltage230V; 50HZ 230V/400V
    Rated surplus operating current10; 30; 100; 300mA
    Selection grade3
    Rated braking capacity10kA
    Rated current6-40A
    Tripping characterB, C, D characteristic curve
    Maximum connected fuse100A gL(> 10kA)
    Environment capabilityAccording to the IEC 1008 standard
    Case protection gradeIP40 after installation
    Electric lifeNot less than 4000 times of breaking and closing
    Mechanical lifeNot less than 2000 times of breaking and closing
    Mechanical Parameter
    Installation modeInstallation at the DIN guide rail of 35mm
    Terminal block capacityGeneratrix thickness 0.8-2mm
    Shell width35mm (1P+N)

    The over-current tripping unit protection feature:


    Sequence NO.ReleaseTest current I/InStart stateTripping timeExpected restlt
    1C1.13InCold statet≤1hNot tripping
    2C1.45InStart right after the serial NO.1 testt<1htripping
    3C2.55InCold state1s<t<60stripping
    4C5InCold statet≤0.1sNot tripping
    5C10InCold statet<0.1stripping

    Loading capacity:




    Our service:

    1. Samples: provided freely


    2. Package: packed in standard cartons, special packing is negotiable


    3. Warranty: 2 years at least


    4. Delivery: within 30days after received the deposit.


    5. OEM, ODM is acceptable


    6. We can help you with any of your idea to design and put it into production.


    7. Provide help for building factories, such as: spare parts, technical questions, financial matter, management problem, approach of sales...

    Quality 1P+N 10kA Residual Circuit Breaker 2 Pole with Over Current RCBO for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Zhejiang KRIPAL Electric Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)